If your Worcester Bosch boiler has stopped and the display shows EA 227, or just 227, it means the boiler tried to light its burner but could not detect a flame. For safety, it has shut the gas off and locked itself out until it is reset.
It is one of the most common Worcester Bosch codes, and it often shows up in cold weather. Sometimes the cause is outside the boiler and easy to put right, such as no gas reaching the house or a frozen condensate pipe. Other times something inside the boiler needs attention from a Gas Safe registered engineer.
This guide is based on Worcester Bosch's own installation manuals, user instructions and frozen condensate advice. It covers what the code means, the safe checks you can do yourself, and when to call an engineer.
We repair and service Worcester Bosch boilers across London, from Barnet and North London outwards.
Smell gas? Don't touch any switches. Open windows, turn off the gas at the meter if you can, leave the property and call the National Gas Emergency Service on 0800 111 999.
What EA 227 means
How the code appears depends on your boiler:
- On Greenstar i, Si and Compact-style boilers, the display shows letters with a three-digit number underneath, such as EA and 227. Worcester's Greenstar i installation manual describes EA 227 as an ignition/ionisation fault: "No ionisation detected after ignition".
- On the newer Greenstar 4000 and 8000 ranges, the display shows the number 227. The Greenstar 4000 and Greenstar 8000 Life manuals describe it as "No flame signal after ignition".
- On some older boilers, such as the Greenstar CDi Classic, you may just see EA, which Worcester's user instructions describe as "flame not detected".
They all point to the same problem. When the boiler gets a call for heat or hot water, it opens the gas valve and sparks the ignition electrode. A separate sensor then checks for a flame by detecting a tiny electrical current through it (this is what "ionisation" means). If the boiler cannot detect that flame signal, it stops the gas and shows the code.
Worcester classes 227 as a locking fault. That means the boiler will not restart on its own. It stays off until someone resets it.

What causes EA 227
Worcester's own user instructions list three common causes for an EA code that you may be able to spot:
- No gas, or low gas pressure. If gas is not reaching the boiler, it cannot light. That could be a supply problem, a prepayment meter that has run out of credit, or a valve that has been turned off.
- A blocked or frozen condensate pipe. Modern condensing boilers drain water away through a plastic pipe, often to a drain outside. In freezing weather that pipe can ice up. Worcester says a frozen or blocked condensate pipe will cause the boiler to shut down, and you may hear it gurgling.
- A blocked flue. The flue is the pipe that takes the waste gases out through the wall or roof. If its outlet is obstructed, the boiler may not light properly.
If none of those is the cause, it is usually something inside the boiler. Worcester's installation manuals tell engineers to check, among other things:
- the gas pressure at the boiler, including whether it drops when the gas valve opens
- the spark (ignition) electrode, its ceramic insulator and lead
- the flame sensing electrode and its lead, and the earth connection
- the gas valve and the supply to it
- the condensate siphon (trap) inside the boiler, which can block
- the air intake, the gas-air ratio and the burner
- the heat exchanger for blockages
All of those are jobs for a Gas Safe registered engineer.
Safe checks you can do yourself
These checks are all done from outside the boiler. Do not take the boiler casing off.
- Check you have gas. Try another gas appliance, such as the hob. If that will not light either, the problem is the gas supply rather than the boiler. Worcester's advice is to contact your gas supplier.
- Check your prepayment meter, if you have one. Worcester's Greenstar 4000 user instructions specifically suggest checking whether your credit has run out. Top up if needed.
- Check the gas valve by the meter. The emergency control valve, usually with a yellow handle, is next to the gas meter. As EDF explains, the gas is on when the handle is in line with the pipe and off when it is at a right angle to the pipe. If it has been knocked to off, turn it back in line with the pipe.
- In cold weather, check the condensate pipe. Look for a white or grey plastic pipe coming out of the wall near the boiler and running to a drain. If it has frozen, thaw it as described below.
- Check the flue outlet. If it is safe to do so, look from the ground at where the flue leaves the wall or roof. Check nothing is blocking it, such as leaves, a nest, snow, or something stacked or growing in front of it.
- Reset the boiler once, using the method for your model below.
- Wait a few minutes. Worcester says to wait two or three minutes for the boiler to restart after a reset.
Thawing a frozen condensate pipe
The pipe usually freezes at its most exposed point: the open end, a bend, or where the pipe sags. Only thaw a pipe that is at ground level and easy to reach. Never try to thaw a pipe that is up a ladder or at height.
- Hold a hot water bottle, a microwaveable heat pack or a cloth soaked in hot water against the frozen section.
- Or pour warm water over it from a watering can or jug. Never use boiling water. Worcester warns it can damage the plastic pipe.
- Take care, as spilt water can freeze and leave a slippery patch.
How to reset your Worcester boiler
The method depends on your model, so check your user manual if you have it:
- Greenstar i models (such as the i System Compact): press the reset button briefly (about one second). "Reset" and a tick appear if it worked.
- Greenstar CDi Classic: hold the reset button for about three seconds. After thawing a condensate pipe, Worcester says to hold it for five seconds.
- Greenstar 4000 and 8000: press the two keys shown in your manual until "Reset" appears on the display.
If the boiler lights and keeps running, the cause may have been temporary, such as a frozen pipe or a supply blip. Keep an eye on it. If the condensate pipe freezes regularly, it is worth getting it rerouted or insulated, which Worcester also recommends.
Don't keep pressing reset
It is tempting to keep resetting, but there is a limit for good reason. If EA 227 comes back after one reset, or after you have thawed the pipe and reset, stop there.
The boiler locks out because it has tried to light and failed. Repeated resets will not fix the cause. On the Greenstar 4000 and 8000, Worcester's manuals say that if five locking faults are reset within 15 minutes, the boiler goes into a "super lock-out" because a potentially safety-critical condition has been detected. At that point it needs an engineer to find and fix the fault.
What not to do
- Do not remove the boiler casing or try to adjust, clean or replace the electrodes, gas valve or anything else inside. All gas work must be done by a Gas Safe registered engineer.
- Do not use boiling water on a frozen condensate pipe. It can crack the plastic.
- Do not climb up to thaw a pipe or check a flue at height.
- Do not keep resetting the boiler if the code keeps coming back.
- Do not cover or block the flue to keep the weather out.
When to call a Gas Safe engineer
Call a Gas Safe registered engineer if:
- EA 227 comes back after one reset
- you have gas at the hob and the condensate pipe is clear, but the boiler still will not light
- the boiler lights, then the code returns a few hours or days later
- the boiler shows a "super lock-out" or keeps showing other fault codes
- the boiler has not been serviced for over a year
An engineer will check the gas pressure at the boiler, inspect the ignition and flame sensing electrodes and their leads, clear the condensate trap, check the gas valve, flue and burner, and finish with a combustion check. Make a note of the full code, including the number under the letters, and your boiler model. Worcester's own user guide gives "EA and 227" as an example of what to quote.
A yearly boiler service is the best way to cut the chances of ignition faults, because the engineer checks and cleans the parts that most often cause them.
If you smell gas, or think you have carbon monoxide symptoms (headaches, dizziness, nausea, feeling better when you leave the house), turn off the gas at the meter if you can, open windows, get outside and call the National Gas Emergency Service on 0800 111 999. Every home with a gas appliance should have a working carbon monoxide alarm.
Similar codes
- EA 229 means the flame was lit but the signal was lost while the boiler was running. Worcester's checks include the gas-air ratio, gas pressure and the flame probe wiring, and a blocked condensate trap can cause it too.
- F7 228 (or 228 on newer models) is the opposite problem: the boiler is detecting a flame signal when there should not be one. That is always one for an engineer.
Need a hand?
Heatmaster London repairs and services Worcester Bosch boilers across London, including Barnet and North London. If EA 227 keeps coming back, or you would rather someone checked it for you, contact us or see our boiler repair and boiler servicing pages. You can also browse our FAQs and the areas we cover. If your boiler simply will not fire up and there is no code, our boiler not working guide may help.
This is the third post in our fault code series. If you have a Vaillant boiler, see our guide to the Vaillant F.22 fault code (low water pressure). For air conditioning, see the Daikin U4 error code.
Sources
- Worcester Bosch, Greenstar i ErP installation, commissioning and servicing instructions (EA 227: no ionisation detected after ignition; EA 229; engineer checks)
- Worcester Bosch, Greenstar 4000 installation and maintenance instructions (227: no flame signal after ignition; locking faults; super lock-out after five resets in 15 minutes)
- Worcester Bosch, Greenstar 8000 Life installation and maintenance instructions (227: no flame signal after ignition)
- Worcester Bosch, Greenstar 4000 user instructions (basic checks including gas and prepayment meter credit; fault reset; extreme cold weather)
- Worcester Bosch, Greenstar i System Compact user instructions (EA causes: gas supply, condensate outlet, flue; reset; quoting "EA and 227")
- Worcester Bosch, Greenstar CDi Classic user instructions (EA: flame not detected; reset; thawing a frozen condensate pipe)
- Worcester Bosch, frozen condensate advice (EA code and gurgling; thaw with warm, not boiling, water)
- EDF, what is a gas safety shut-off valve (on and off positions of the valve by the meter)